Skip to main content

Backwater lifting station Ecolift

w/o socket, Floor slab, black

The backwater lifting station for faecal and non-faecal wastewater is equipped with one pump and one motor-driven closure system. The pipe cross-section is normally open and the water drains to the sewer via natural fall. Backwater is detected by an optical probe, which causes the motor-driven closure system to close automatically. During the backwater phase, the water drains via a pressure pipe, which carries the wastewater above the backwater level and into the sewer. Connection hole in the drain body for installation in the ground, incl. seal for pressure pipe and cable conduit. The station is controlled by a user-friendly control unit, which is optionally integrated in the building management system via a potential-free contact, or alarm and collective fault messages can be output via a GSM interface.

  • Hybrid function: uses the natural fall to the sewer - pump is only used in case of backwater
  • Quiet and energy-saving
  • Double safety due to backwater flap and pressure pipe
Item no. 21000S
GTIN 4026092058558
Price group 20

Backwater lifting station Ecolift w/o socket, Floor slab, black
The backwater lifting station for faecal and non-faecal wastewater is equipped with one pump and one motor-driven closure system. The pipe cross-section is normally open and the water drains to the sewer via natural fall. Backwater is detected by an optical probe, which causes the motor-driven closure system to close automatically. During the backwater phase, the water drains via a pressure pipe, which carries the wastewater above the backwater level and into the sewer. Connection hole in the drain body for installation in the ground, incl. seal for pressure pipe and cable conduit. The station is controlled by a user-friendly control unit, which is optionally integrated in the building management system via a potential-free contact, or alarm and collective fault messages can be output via a GSM interface. Type of wastewater: wastewater with sewage Installation situation: floor slab installation Version: Odour trap: Multistop Emergency closure: yes Pump control: Control unit Passage seal for conduit pipe (DN): 50 mm Delivery state: Pre-mounted for final assembly on site (pumps and sensor system must be fitted on site and control unit must be connected) Number of motor-driven backwater flaps: 1 General characteristics: Nominal size (DN): - Colour: black Approval: Z-53.2-487 Dimensions: Length: 590 mm Width: 590 mm Cutout dimension, length: 750 mm Cutout dimension, width: 750 mm Tank: Pressure pipe connection (OD): 40 mm Installation depth: 486 - 640 mm Groundwater resistant from lower edge of base section: 3,000 mm Nominal pressure (PN): 6 Drain body: Socket version: optional Vertical adjustment: vertically adjustable upper section Coverage features: Type of cover: Cover plate with slotted cover Cover material: Polymer Colour of cover: black Drainage function: yes Load class: L 15 (EN 1253-1) Length: 366 mm Width: 366 mm Locking: Lock & Lift Pumping device: Pump: SPZ 1000 Number of pumps: 1 Max. pumping capacity: 11.5 m3/h Max. pumping height: 10 m Operating mode: S3 - 50 % Power P1: 1.2 kW Power P2: 0.69 kW Speed: 2,800 U/min Type of fuse required (electrical protection): C 16 A Max. temperature (permanent) of conveyed material: 40 °C Connection type: coded plug Weight: 10 kg Impeller type: Macerator Length of mains cable for pump: 5 m Rated current: 5.2 A Protection class (pump): IP 68 (3m/48h) Protection class: I Type of pump connection cable: H07RN-F 3G 1.0 mm2 Temperature monitoring: integrated Cos phi - power factor: 0.97 Insulation class: F Vertical drop between inlet and outlet: 9 mm Motor type: KSM 140 Protection class motor: IP 68 (3m/48h) Protection class probe: IP 68 (3m/48h) Control: Control unit: Comfort Operating voltage: 230 V Mains frequency: 50 Hz Self-diagnosis system (SDS): yes Battery buffering: yes Multi-line display: yes Log book function: yes USB interface: no GSM interface: no Potential-free contact: yes Standby power: 5 W Protection class control unit: IP 54 Length of mains cable for control unit: 1.4 m Type of level measurement: optical Level measurement instrument: optical probe Alarm sensor: optical probe

Installation Video

  Title Item no.  
Staufix Premium Spigot DN 100 83081 Show
Staufix Premium Spigot DN 125 83082 Show
Staufix Premium Spigot DN 150 83083 Show
Staufix Premium Spigot DN 200 83084 Show
Staufix Premium Socket DN 100 83085 Show
Staufix Premium Socket DN 125 83086 Show
Staufix Premium Socket DN 150 83087 Show
Staufix Premium Socket DN 200 83088 Show
  Title Item no.  
  Title Item no.  
Remote signal generator 20 m cable, 2x0.75 q 20162 Show
Pressure pipe set 5 m pressure hose, DA 40 mm 28040 Show
Clearance code for potential-free contact 80077 Show
10 m probe cable extension set 80889 Show
Cable extension set for motor 10 m 80890 Show
Cable prolongation set for pump 10 m 80891 Show
Extension section H: 200 mm 83070 Show
Extension section H: 234 mm, with flange and counter-flange 83073 Show
Extension section H: 360 mm, with central flange 83075 Show
Waterproof concrete install. kit OD: 40 mm, for building contractors 83077 Show
  Title Item no.  
Cover Ecolift outlet side 21056 Show
Pump cover inlet side 28054 Show
Vent for Pumpfix Premium 28060 Show
Active carbon filter 28061 Show
Pumpfix F Control Unit Komfort - IP 54 28071 Show
KTP1000 cutting assembly replacement set 28075 Show
Replacement pump AqualiftF/Pumpfix F 28351 Show
One-handed closure for backflow preventer 680018 Show
Battery 9 V block 680034 Show
Flap holder for motor-driven and mechanical flap 680101 Show
Pressure pipe connection Ecolift, installation in floor slab 680105 Show
Seal for upper section, from 07/2014 680150 Show
Drain connection DN 70, with seal 680215 Show
Seal for cover plate, System 330 mm 686114 Show
Gasket set (Pumpfix, Ecolift) 70319 Show
Motor-driven backwater flap Premium 80038 Show
Insert part f. motor-driven flap Premium 80039 Show
Staufix FKA drive motor (KSM 140) 5m 80076 Show
Replacement set optical probe 80888 Show
Adapter set optical probe 80892 Show
Cover plate 366 x 366 mm w. flat drain body, Multistop, black 830046 Show
Upper section System 400 830065 Show
  • Groundwater resistant from lower edge of base section (ATTR-B12): 3,000  MMT
  • Installation situation (ATTR-1): floor slab installation
  • Country of origin (ATTR-322): DE
  • Area of application (ATTR-264): drainage
  • Pump type (ATTR-265): Freestanding pump
  • Pump shaft position (ATTR-266): vertical
  • Pump design (ATTR-267): Dry rotor pump
  • Pump hydraulics (ATTR-268): single stage
  • Pump suction characteristic (ATTR-269): non-self-priming
  • Pump drive (ATTR-270): E-motor for alternating current
  • E-motor, type of startup (ATTR-271): direct
  • Pump casing material (ATTR-272): Polymer
  • Upper tolerance of the nominal frequency (+) (ATTR-275): 3  PROZ
  • Lower tolerance of the nominal frequency (-) (ATTR-276): 2  PROZ
  • Pump electrical connection (ATTR-277): 1/N/PE 230V
  • Motor pump shaft (ATTR-279): continuous
  • Shaft seal (ATTR-280): RSSR
  • Minimum pumped media temperature (ATTR-282): 0  CEL
  • Maximum operating pressure (Pmax) (ATTR-283): 1,000  HPA
  • Minimum speed for speed adjustment (ATTR-284): no speed adjustment
  • Start-up current (ATTR-285): 14.9  AMP
  • Vertical installation (ATTR-286): yes
  • Pump (ATTR-4): SPZ 1000
  • Number of pumps (ATTR-181): 1
  • Impeller type (ATTR-8): Macerator
  • Type of pump connection cable (ATTR-N2): H07RN-F 3G 1.0 mm2
  • Type of fuse required (electrical protection) (ATTR-N3): C 16 A
  • Max. permissible switching frequency (ATTR-162): 20  1PH
  • Operating mode (ATTR-10): S3 - 50 %
  • Power P1 (ATTR-F4): 1.2  KWT
  • Power P2 (ATTR-F5): 0.7  KWT
  • Speed (ATTR-F2): 2,800  UMIN
  • Rated current (ATTR-N5): 5.2  AMP
  • Max. pumping capacity (ATTR-F7): 11.5  MQH
  • Max. pumping height (ATTR-F8): 10  MTR
  • Max. temperature (permanent) of conveyed material (ATTR-132): 40  CEL
  • Protection class (ATTR-133): I
  • Connection type (ATTR-N1): coded plug
  • Protection class (pump) (ATTR-125): IP 68 (3m/48h)
  • Length of mains cable for pump (ATTR-11): 5  MTR
  • Temperature monitoring (ATTR-135): integrated
  • Weight (ATTR-191): 10  KGM
  • Cos phi - power factor (ATTR-192): 1.0
  • Insulation class (ATTR-193): F
  • Expected service life (hours of operation) (ATTR-194): 5,000  HUR
  • Expected service life (number of switching cycles) (ATTR-195): 150,000
  • Nominal size (DN) (ATTR-118): -
  • Net weight (ATTR-A3A): 28  KGM
  • Gross weight (ATTR-A3B): 33.5  KGM
  • Installation depth (ATTR-B2_VB): 486  MMT
  • Vertical adjustment (ATTR-177): vertically adjustable upper section
  • Length (ATTR-A6A): 590  MMT
  • Width (ATTR-A6B): 590  MMT
  • Cutout dimension, length (ATTR-160): 750  MMT
  • Cutout dimension, width (ATTR-161): 750  MMT
  • Volume (ATTR-320): 0.3  MTQ
  • Packaging dimension: length (ATTR-325): 785  MMT
  • Packaging dimension: width (ATTR-326): 615  MMT
  • Packaging dimension: height (ATTR-327): 550  MMT
  • Dimensions (ATTR-323): 785X615X550MM
  • Number of packages (ATTR-321): 1
  • Odour trap (ATTR-115): Multistop
  • Emergency closure (ATTR-153): yes
  • Pump control (ATTR-134): Control unit
  • Socket version (ATTR-233): optional
  • Control unit (ATTR-S2): Comfort
  • Self-diagnosis system (SDS) (ATTR-S5): yes
  • Battery buffering (ATTR-S6): yes
  • Multi-line display (ATTR-S7): yes
  • Log book function (ATTR-S8): yes
  • USB interface (ATTR-S9): no
  • GSM interface (ATTR-S10): no
  • Potential-free contact (ATTR-S11): yes
  • Length of mains cable for control unit (ATTR-S12): 1.4  MTR
  • Operating voltage (ATTR-S13): 230  VLT
  • Mains frequency (ATTR-S14): 50  HTZ
  • Protection class control unit (ATTR-S4): IP 54
  • Alarm sensor (ATTR-S1): optical probe
  • Type of level measurement (ATTR-7A): optical
  • Level measurement instrument (ATTR-7B): optical probe
  • Pressure pipe connection (OD) (ATTR-B18): 40  MMT
  • Nominal pressure (PN) (ATTR-B18B): 6
  • Type of cover (ATTR-A21): Cover plate with slotted cover
  • Colour of cover (ATTR-A2A): black
  • Load class (ATTR-A2B): L 15 (EN 1253-1)
  • Locking (ATTR-A2D): Lock & Lift
  • Cover material (ATTR-A2E): Polymer
  • Drainage function (ATTR-A2H): yes
  • Length (ATTR-A2M): 366  MMT
  • Width (ATTR-A2N): 366  MMT
  • Passage seal for conduit pipe (DN) (ATTR-184): 50  MMT
  • Declaration of Performance (DOP) (ATTR-292): 009-036
  • Wastewater quantity (ATTR-310): Medium
  • Protection strategy (ATTR-311): Central protection
  • Type of wastewater (ATTR-6): wastewater with sewage
  • Position relative to sewer (ATTR-309): Gradient to the sewer
  • Function in the event of backwater (ATTR-312): Drains in the event of backwater
  • Protection class probe (ATTR-175): IP 68 (3m/48h)
  • Colour (ATTR-102): black
  • Protection class motor (ATTR-174): IP 68 (3m/48h)
  • Motor type (ATTR-120B): KSM 140
  • Approval (ATTR-A5): Z-53.2-487
  • CE marking (ATTR-A5B): no
  • Number of motor-driven backwater flaps (ATTR-3A): 1
  • External monitoring (ATTR-A8): LGA
  • Vertical drop between inlet and outlet (ATTR-176): 9  MMT
  • Delivery state (ATTR-189): Pre-mounted for final assembly on site (pumps and sensor system must be fitted on site and control unit must be connected)
  • Declaration of conformity (ATTR-289): yes
  • Brand (M-ATTR-001): KESSEL
  • Product group (M-ATTR-002): Hybrid lifting stations
  • Product type (M-ATTR-003): Backwater lifting station
  • Product family (M-ATTR-004): Ecolift
  • Product name (M-ATTR-005): Ecolift
  • Standby power (ATTR-S20): 5  WTT